防火門的設置及運用場合
防火門的設置應相符以下劃定:
The setting of fire doors shall comply with the following provisions:
1、設置在修建內常常有人通行出的防火門宜采取常開防火門。常開防火門應能在火警時自行封閉,並應具有旌旗燈號反應的功效。
1, set up in the building, often through the fire doors should be used to open fire doors. Normally open fire doors should be closed automatically in case of fire and should have the function of signal feedback.
2、除許可設置常開防火門的的地位外,其他地位的防火門均應采取常閉防火門,常閉防火門應在其顯著地位設置“堅持防火門封閉”等提醒。
2, in addition to allowing the installation of normally open fire doors of the location, other locations of fire doors should be used normally closed fire doors, normally closed fire doors should be placed in its obvious position "keep fire doors closed" and other tips.
3、應由常開防火門地點防火分區內的兩只自力的火警探測器或一只火警探測器與一只手動火警報警按鈕的報警旌旗燈號,作爲常開防火門封閉的聯動觸發旌旗燈號,聯動觸發旌旗燈號應由火警報警掌握器或消防聯動掌握器收回,並應由消防聯動掌握器或防火門監控器聯動掌握防火門封閉
3, two fire detectors shall normally open fire doors of fire compartments independent or a fire detector and a manual fire alarm alarm button, linkage as the normally open fire doors closed trigger signal, trigger signal by the linkage of the fire alarm controller or fire linkage controller issued, and by fire or fire linkage controller the linkage control of fire door closed door monitor
4、分散通道上各防火門的開啓、封閉及毛病狀況旌旗燈號應反應至防火門監控器。
4. The opening, closing and failure status of the fire doors on the evacuation passageway shall be fed back to the fire door monitor.
5、防火門監控器應設置在消防掌握室內,未設置消防掌握室的應設在有人值班的場合,監控分機可設在電氣豎井或樓層配電間等處。
5, fire door monitor should be set up in the fire control room, not set fire control room should be located in someone on duty place, monitoring extension can be located in electric shaft or floor distribution room.
6、電動開門器的手動掌握按鈕應設置在防火門內側牆面上,距門不宜跨越0.5m,底邊距空中高度宜爲0.9m~1.3m。
6, electric door opener manual control button should be set in the fire door on the wall, from the door should not exceed 0.5m, the bottom edge from the ground height should be 0.9m ~ 1.3m.
7、防火門監控器的設置應相符火警報警掌握器的裝置設置請求。
7, fire door monitor settings should comply with fire alarm controller installation and installation requirements.
防火門監控器用于顯示並掌握防火門翻開、封閉狀況的掌握裝配。
A controller for displaying and controlling the opening and closing of a fire door.
8、防火門聯動閉門器可以或許在收到指令後將處于翻開狀況的防火門封閉,並將其狀況信息反應至防火門監控器的電動裝配。
8, fire door linkage door closer to receive the instructions will be opened in the fire door closed, and its status information back to the fire door monitor electric device.
9、防火門電磁釋放器
9. Fire door electromagnetic releaser
使常開防火門堅持翻開狀況,在收到指令後釋放防火門使其封閉並將本身的狀況信息反應至監控器的電動裝配。
The normally open fire door is kept open, and the fire door is released after receiving the instruction, and the state information of the door is turned back to the electric device of the monitor.
10、防火門門磁開關
10, fire door switch
用于監督防火門的開閉狀況,並能將其狀況信息反應至防火門監控器的裝配。
A device for monitoring the open and closed condition of a fire door and returning its status information to a fire door monitor.
11、防火門毛病狀況
11. Fire door failure status
防火門處于非正常翻開的狀況或非正常封閉的狀況。
The condition of being abnormally open or abnormally closed.
哪些場合要設置防火門:
Which places should be equipped with fire doors?:
::
::
1、廠房內的原棉開包、清花車間與廠房內其他部位之間均應采取耐火極限不低于2.50h的防火隔牆分隔,須要開設門、窗、洞口時,應設置甲級防火門、窗。
1, plant cotton bag, among other parts of flower shop and workshop should use the fire resistance limit of not less than 2.50h of the fire wall separated, need to open doors and windows, the entrance, should be set up first class fire door and window.
2、廠房內的丙類液體中央儲罐應設置在零丁房間內,其容量不該大于5m³。設置中央儲罐的房間,應采取耐火極限不低于3.00h的防火隔牆和1.50h的樓板與其他部位分隔,房間門應采取甲級防火門。
C liquid storage tank 2, intermediate workshop should be set in a separate room, its capacity should not exceed 5m fand. Rooms with intermediate storage tanks shall be equipped with fire-resistant barriers, not less than 3.00h fireproof partitions, and 1.50h floors shall be separated from other parts, and fire doors shall be adopted in room doors.
3、兩座1、二級耐火品級的廠房,當相鄰較低一面外牆爲防火牆且較低一座廠房的屋頂無天窗,屋頂的耐火極限不低于1.00h,或相鄰較高一面外牆的門、窗等啟齒部位設置甲級防火門、窗或防火分隔水幕設置防火卷簾時,甲、乙類廠房之間的防火間距不該小于6m;丙、丁、戊類廠房之間的防火間距不該小于4m。
3, two grade one or two fire resistance rating of the plant, when the adjacent lower outer wall is the firewall and lower the roof without a roof, the roof of the fire resistance limit of not less than 1.00h or higher, adjacent side wall the door and window openings set a fire doors, windows or fire compartment fire shutter when setting water curtain fire, the distance between a and B plants should not be less than 6m; the fire spacing between C and D, e plant should not be less than 4m.
4、有爆炸風險區域內的樓梯間、室外樓梯或有爆炸風險的區域與相鄰區域連通處,應設置門鬥等防護辦法。門鬥的隔牆應爲耐火極限不該低于2.00h的防火隔牆,門應采取甲級防火門並應與樓梯間的門錯位設置。
4, there are dangerous areas within the stairwell, outdoor staircase or explosion danger areas and adjacent areas connected, should set up the door, bucket and other protective measures. The partition of the fire door should be fire-resistant, not less than 2.00h fireproof partition, the door should adopt grade a fireproof door, and should be set with the door of the staircase.
5、地下或半地下廠房(包含地下或半地下室),當有多個防火分區相鄰安排,並采取防火牆分隔時,每壹個防火分區可應用防火牆上通向相鄰防火分區的甲級防火門作爲第二平安出口,但每壹個防火分區必需至多有1個縱貫室外的自力平安出口。
5, underground or semi underground powerhouse (including underground or semi basement), when there are multiple fire compartments arranged adjacent to, and the firewall, the firewall can use each fire zone adjacent to the fire district as the second class a fire door fire exits, but each partition must have at least 1 straight outdoor independent safety exit.
6、地下或半地下倉庫(包含地下或半地下室)的平安出口不該少于2個;當修建面積不大于100m2時,可設置1個平安出口。
6, underground or semi underground storage (including underground or semi basement) safety exit should not be less than 2; when the construction area is not greater than 100m2, you can set 1 safety exit.
7、 地下或半地下倉庫(包含地下或半地下室),當有多個防火分區相鄰安排並采取防火牆分隔時,每壹個防火分區可應用防火牆上通向相鄰防火分區的甲級防火門作爲第二平安出口,但每壹個防火分區必需至多有1個縱貫室外的平安出口。
7, underground or semi underground warehouse (including underground or semi basement), when there are multiple fire compartment disposed adjacent to and by firewall, each fire zone can use the firewall to the adjacent fire class a fire door as the second exit, but each partition must have at least 1 straight outdoor safety exit.
8、相鄰兩座修建中較低一座修建的耐火品級不低于二級且屋頂無天窗,相鄰較高一面外牆淩駕較低一座修建的屋面15m及以下規模內的啟齒部位設置甲級防火門、窗,或設置相符現行國度尺度《主動噴水滅火體系設計標準》GB50084劃定的防火分隔水幕或本標準第6.5.3條劃定的防火卷簾時,其防火間距不該小于3.5m;關於高層修建,不該小于4m。
The fire resistance rating of 8, two adjacent building in the lower building is not less than two and no roof skylight, adjacent high side wall openings high roof 15m and below the lower range of a building set within the class a fire door, window, or set up in accordance with current national standard "automatic sprinkler system design the provisions of the standard" GB50084 fire protection water curtain or the standard provisions of article 6.5.3 of the fire shutter, the fire spacing should not be less than 3.5m; for the high-rise buildings, should not be less than 4m.
9、與四周連通空間應停止防火分隔:采取防火隔牆時,其耐火極限不該低于1.00h;采取防火玻璃牆時,其耐火隔熱性和耐火完全性不該低于1.00h。采取耐火完全性不低于1.00h的非隔熱性防火玻璃牆時,應設置主動噴水滅火體系停止掩護;采取防火卷簾時,其耐火極限不該低于1.00h,與中庭相連通的門、窗,應采取火警時能自行封閉的甲級防火門、窗。
9, with the surrounding space should be fire-resistant partition: the use of fire wall, its fire resistance should not be less than 1.00h; the use of fire-resistant glass wall, its fire resistance, heat insulation and fire integrity should not be less than 1.00h. Using non thermal insulation fireproof glass wall fire integrity of not less than 1.00h when the sprinkler system should be set to protect the fire shutter; when the fire resistance should not be less than 1.00h, the door and the window is communicated with the atrium, should use the fire to class a fire door and window self closing.